ZF Series Negative Pressure Vacuum Pump Station

The ZF series negative pressure vacuum pump (also known as a vacuum generation device, negative pressure station, etc.) is a complete system that uses one or two water ring vacuum pumps as vacuum generation equipment, with a vacuum tank as the vacuum storage device. For applications where a vacuum source is frequently needed but the required pumping capacity is not very large, this system greatly saves energy compared to direct vacuum pump use and effectively extends the service life of the vacuum pump.

description

This equipment serves as a negative pressure vacuum pump system for medical gas central stations in large and medium-sized hospitals across China. It is also widely applied as a vacuum source in various fields, including vacuum stations in the chemical and pharmaceutical industries, canning systems in light industries, negative pressure molding for rubber and plastic components in the automotive sector, flame-retardant conveyor belt impregnation in coal mining, and vacuum casting processes in foundries (such as V method, VRH, and V-EPC).

丨Main Features

  1. After the initial startup, the entire operation of this negative pressure vacuum pump system can be fully automated. During operation, the vacuum level throughout the vacuum system fluctuates within an allowable range, which can be adjusted according to user requirements.
  2. The system automatically controls itself without manual intervention and can automatically seal the vacuum system in the event of a power outage.
  3. It is equipped with an air-water separator, which conserves water resources and reduces environmental pollution.
  4. The vacuum tank can be designed in either horizontal or vertical configurations according to site requirements, offering flexible installation options.
Model Vacuum pump area Recommended vacuum pump
(water ring vacuum pump)
Power KW
kw
Vacuum Fluctuation Range MPa Ultimate Vacuum Pressure MPa Interface Flange Size (mm)
DN d3 d2 n d1
ZF-0.3 0.3 2BV2060x2 units 0.81kwx2 0-0.09 -0.098 40 100 8
0
4 9
SK-0.4×2 units 1.5kwx2 0-0.08 -0.093
ZF-0.5 0.5 2BV-2061×2 units 1.45kwx2 0-0.09 -0.098 50 110 90 4 9
SK-0.8×2 units 2.2kwx2 0-0.08 -0.093
ZF-1 1 2BV-5110×2 units 4kwx2 0-0.09 -0.098 80 145 125 4 9
SK-1.5×2 units 4kwx2 0-0.08 -0.093
ZF-1.5 1.5 2BV-5110×2 units 4kwx2 0-0.09 -0.098 80 145 125 4 9
SK-1.5×2 units 4kwx2 0-0.08 -0.093
ZF-2 2 2BV-5110×2 units 4kwx2 0-0.09 -0.098 80 145 125 4 9
SK-3×2 units 5.5kwx2 0-0.08 -0.093
ZF-3 3 2BV-5111×2 units 5.5kwx2 0-0.09 -0.098 100 165 145 4 12
SK-3×2 units 5.5kwx2 0-0.08 -0.093
ZF-5 5 2BV-5121×2 units 7.5kwx2 0-0.09 -0.098 100 165 145 4 12
SK-6×2 units 11kwx2 0-0.08 -0.093